To those not acquainted with solar air-conditioning (SAC), the technologies might seem to be a contradiction in terms. In all SAC solar heat is used to drive a cooling process. Generally, SAC can be distinguished into:
Closed cycle systems
Closed cycle systems are equipped with thermally driven chillers, which provide chilled water that is either used in air handling units to supply cooled and dehumidified air or that is distributed via a chilled network to decentralized room installations such as fan coils or chilled ceilings. Available thermally driven chillers on the market are absorption chillers, which are most common, and adsorption chillers, offered currently by few manufacturers only. A component, necessary in all chilled water systems, is a heat rejection system.
Open cycle systems
Open cycle systems allow complete air-conditioning by supplying cooled and dehumidified air. The “refrigerant” is always water, which is brought into direct contact with the atmosphere. The most common open systems are desiccant cooling systems with a rotating dehumidification wheel and a solid sorbent.
Among the thermally driven cooling systems, closed cycle systems have currently a central position. According to a survey in 2003, approx. 71 % of the installations were equipped with chillers (63 % using absorption technology and 8 % using adsorption chillers). Besides, 29 % of the installations are desiccant cooling systems.By the way, solar cooling systems have a fast growing market with several new actors. New interesting developments and concepts are appearing in the different technologies.In a near future, the barriers to overcome are the organisation of the sector, the cost reductions and the adaptation of the machines and the main components to technical specifications of solar cooling systems.
Type of refrigerant cycle | Closed Refrigerant flows | Open Refrigerant is in | ||
Principle | Chilled water | Dehumidification of air and evaporative cooling | ||
Phase of sorbent | Solid | Liquid | Solid | Liquid |
Typical material duo | Water - silica gel | Water - water/lithium bromide, ammonia- water | Water - silica gel / Water - lithium chloride | Water - calcium chloride, Water - lithium chloride |
Available technology | Adsorption chiller | Absorption chiller | Desiccant cooling | Close to market introduction |
Typical cooling capacity | 5.5 - 500 kW | 4.5 kW - 5 MW | 20 - 350 kW (per module) | - |
Typical coefficient of performance * | 0.5 - 0.7 | 0.6 - 0.75 | 0.5 - > 1 | > 1 |
Typical driving temperature | 65 - 90 °C | 80 - 110 °C | 50 - 95 °C | 50 - 70 °C |
Solar collectors | tubes, flat plate | tubes, flat plate | Flat plate, air collectors | Flat plate, air collectors |
* Coefficient of Performance (COP) = chilling capacity / driving heat