Description of the application

The solar cooling plant has been installed during 2007 in an office and laboratory building in Barcelona.
This building is part of the Public Health Agency of Barcelona (PERACAMPS building). The building has a large thermal demand all year long due to its function as laboratory and office.

General description of the system

The system consists of a LiBr absorption chiller with 35 kW of cooling capacity, 82 m² of selective flat-plate collector, two 3 m³ tanks to store the solar production and 1 m³ tank to store the cooling production. This system will contribute to cover 20% of the total thermal demand of the building (cooling, heating and domestic hot water). The remaining demand will be covered by the former installation with a gas boiler and an electric vapour compression chiller. The installation has been designed including two tanks that can be connected in parallel or in series. Depending on the season of the year, different control strategies are possible to drive the solar production towards heating demand or cooling demand. The two tanks can work in parallel with two different set-point temperature levels, particularly during spring and autumn when both heat and cold demand are required during the same day in the building.

Central air-conditioning unit

Technology

closed cycle

Nominal capacity

35 kWcold

Type of closed system

absorption

Brand of chiller unit

Yazaki

Chilled water application

fan coils

Dehumidification

yes

Heat rejection system

wet cooling tower 98 kW

Solar thermal

Collector type

flat-plate

Brand of collector

Wagner Solar

Collector area

81.9 m2 aperture area

Tilt angle, orientation

30°, 19° west

Collector fluid

water-glycol 30%

Typical operation temperature

80 °C (driving heat for cooling operation)

Configuration

Heat storage

2 x 3 m3 water tanks

Cold storage

1 m³ water tank

Auxiliary heating support

508 kW gas boiler

Use of auxiliary heating system

domestic hot water, space heating in winter

Auxiliary chiller

yes

- type

compression chiller

- capacity

323 kWcold

System performance

Due to the recent installation of the system, there is still no integrated data available. However, the expected results are as follow:
Performance data    
Source:    TRNSYS simulation

  • Demand: Cooling: 231 MWh/a
                   Heating: 85 MWh/a
                   DHW: 24 MWh/a
  • Solar contribution: Cooling: 4%
                               Heating: 20%
                               DHW: 68%
  • Primary energy savings: 72 MWh/a

System reliability and overall success of the installation

Not available yet

General information

Type of building  laboratories
Location  Barcelona, Spain
In operation since  July 2007
System promoted by  Agència Local d'Energia de Barcelona, AEB
Air-conditioned area  2.600 m2
Capacity  35 kW absorption chiller

Figures

View at absorption chiller (left), cold storage, cooling tower and first row of solar collectors (front)
View at absorption chiller (left), cold storage, cooling tower and first row of solar collectors (front)
View of hot storage tanks, pumps, and expansion vessel (right)
View of hot storage tanks, pumps, and expansion vessel (right)
Scheme during the summer mode operation. Grey dot lines for pipes out of operation
Scheme during the summer mode operation. Grey dot lines for pipes out of operation

Clicking an image opens the gallery view.


Specific information

Further specific information about the system are included in the filled in technical questionnaire.